Last updated: September 2026 | SmartPower Electronics — manufacturer of load banks & power testing equipment since 2010
Size your load bank at 125% of the rated power of the device under test. For a 400 kW diesel generator, choose a 500 kW load bank; for a 100 kW generator, a 125–150 kW unit is the practical sweet spot. The 25% margin lets you reach true 100% load without running the equipment at its absolute limit, and leaves headroom for voltage/frequency tolerance and future expansion. For UPS and data-center systems, size on real power (kW = kVA × power factor, typically 0.8) and confirm the load type (resistive vs reactive vs electronic) matches what you are testing.
Read on for the step-by-step method, worked examples, and the mistakes that cost buyers the most.
A load bank is a device that consumes electrical power and converts it to heat, creating a controlled, adjustable load for testing a power source — a generator, UPS, inverter, or battery system. It answers one question with proof: "Can this power system actually deliver what its nameplate promises, under real load?"
You need one when you must:
Rule of thumb used by field engineers: load bank capacity = rated power of the device under test × 1.25. Example: for a 400 kW diesel generator → 500 kW load bank.
Find the continuous prime/standby rating on the genset nameplate (kW or kVA). Then define the test:
| Test objective | Typical load target |
|---|---|
| Commissioning / acceptance | 100% of rated for 1–2 hours, often with a 110% overload step for 10 min |
| Monthly maintenance exercise (EPSS) | 30% of nameplate for 30 minutes (e.g., NFPA 110 jurisdictions) |
| Repair verification | 50–100% in stepped ramps |
| Production-line aging | Continuous at 80–100% |
Why not exactly 100%? Three reasons:
| Device under test | Recommended load bank size |
|---|---|
| 100 kW diesel generator | 125–150 kW |
| 400 kW diesel generator | 500 kW |
| 800 kW standby genset (data center) | 1000 kW (resistive, PF 0.8 factored) |
| 250 kVA UPS (PF 0.8) | 200 kW resistive + optional reactive bank for output testing |
See the comparison table below. A pure generator test usually needs resistive elements; UPS and rotary systems need reactive (RLC) capability to simulate motors and lagging power factor.
Confirm the load bank's input matches your site: AC 230/400 V, single/three-phase, 50/60 Hz (dual-frequency units exist), plus the correct plug/socket standard. For permanent data-center installations, choose terminal-box or busbar connection; for field work, a portable unit with industrial sockets.
Modern load banks offer:
| Resistive | Reactive (R/L/C) | Electronic | |
|---|---|---|---|
| What it simulates | Lights, heaters — pure real power | Motors, transformers, UPS — leading/lagging power factor | Batteries, chargers, PV inverters — CC/CV/CP/CR profiles |
| Best for | Generator & UPS full-load testing | Data centers, marine, rotary UPS | R&D, production-line aging, EV charging |
| Power factor | 1.0 | Adjustable (e.g., 0.8 lag) | Programmable |
| Cost | Lowest | Higher | Highest |
| Recommendation | Routine maintenance (best value) | Data center & comms backup | R&D teams |
UPS output testing is about real power, not apparent power:
Data-center sizing shortcut: total IT load × 1.25, then round up to the next standard unit size, and plan for parallel connection if you may exceed 1,000 kW later.
A 500 kW load bank (400 kW × 1.25). This reaches 100% load comfortably and leaves margin for voltage drop and ambient derating.
At exactly 100%, alternator voltage drop and ambient conditions can prevent you from ever reaching full rated kW — the test fails for the wrong reason. The 25% margin is standard field practice.
Often yes, if voltage/frequency match. Use a resistive unit for steady-state generator and UPS inverter tests; add reactive (RLC) capability if you need to simulate lagging power factor for rotary UPS or data-center plants.
Routine generator/UPS maintenance → resistive (best value). Data center and marine backup → resistive + reactive. R&D and production aging of batteries/chargers/inverters → electronic.
Convert to real power first: kW = kVA × PF (typically 0.8). A 250 kVA UPS needs a 200 kW load bank to be fully exercised.
At least IP54–IP55 for containerized outdoor units. For permanent outdoor installations in humid climates, choose a model with built-in dehumidification/heating, and perform an insulation-resistance test before first use.
Rent if you test once or twice a year and transport is easy. Buy if you have recurring code-required testing, a production line, or multiple sites — a 500 kW unit typically pays for itself in under two years of rental-equivalent usage.
Size for your next genset or UPS, not the current one — one load bank can serve a fleet of smaller units, so oversizing once (e.g., 1000 kW instead of 800 kW) avoids a second purchase later. Ensure the unit supports parallel connection for further expansion.
Sizing a load bank is a 6-step process: know the rated power → apply the 1.25 margin → pick the load type → match voltage/phase/frequency → choose control & step resolution → plan cooling and clearances. For generator testing, start at 125% of rated power with a resistive unit; for UPS and data centers, convert kVA to kW at PF 0.8 and add reactive capability when the load profile demands it.
Since 2010, SmartPower Electronics has manufactured load banks from 3 kW to 2,000 kW (AC/DC, resistive, RLC and electronic types) with CE, CCC and UL certification, trusted in 80+ countries for generator, UPS, data-center, solar, and EV-charger testing. Our engineering team can review your sizing sheet and recommend a standard or custom configuration — including touch-screen control, remote PC software, and IP54 outdoor containerized builds.
Need a second opinion on your sizing calculation? Contact our engineers or browse the full load bank range. For day-to-day questions, the load bank FAQ covers capacity, IP ratings, maintenance and calibration.
+86 13690182704
Monday to Friday
sales@smartpower-test.com
+852 30697480
Monday to Friday
sales@smartpower-test.com
Sophia